Technical data
Voltage tester | GVT 1000-15 |
|---|---|
Article number | 3 601 K77 8.. |
Measuring range for voltage | 12 to 1000 V AC/DC |
Frequency rangeA) | 10 to 1000 Hz |
Maximum operating time | 30 s |
Recovery time | 240 s |
Test current peak value | ≤ 3.5 mA |
Continuity testing | ● |
General | |
Operating temperature | –10 °C to +50 °C |
Storage temperatureB) | −40 °C to +70 °C |
Relative air humidity max. | 90 % |
Max. altitude | 2000 m |
Pollution degree according to IEC 61010-1C) | 2 |
WeightD) | 0.40 kg |
Protection rating | IP 65 |
Safety class | CAT IV 600 VE) CAT III 1000 VF) |
Dimensions | 261 x 39 x 86 mm |
Non-rechargeable batteries | 2 x 1.5 V AAA LR 03 |
- A)
According to EN 61243-3:2014, f = 16 ⅔ ... 500 Hz
- B)
without batteries
- C)
Only non-conductive deposits occur, whereby occasional temporary conductivity caused by condensation is expected.
- D)
Weight without batteries
- E)
MEASUREMENT CATEGORY IV is applicable to test and measuring circuits connected to the supply point of the building's low-voltage mains installation.
- F)
MEASUREMENT CATEGORY III is applicable to test and measuring circuits connected to the distribution part of the building's lowvoltage mains installation.